the star-connected winding of the transformer. 87LOZREF is normally applied when the
transformer is grounded solidly or through low-impedance resistor (NER). 87LOZREF
can be also applied on the delta side of the transformer if a grounding transformer (zig-zag
transformer) is used there. In 87LOZREF, the difference of the fundamental component
of all three phase currents and the neutral current is provided to the differential element to
detect the ground fault in the transformer winding based on the numerical stabilized
differential current principle.
Connection of current transformers
The connections of the primary current transformers are designated as "Type 1" and "Type
2".
•
If the positive directions of the winding 1 and winding 2 protection relay currents are
opposite, the
CT connection type
setting parameter is "Type 1". The connection
examples of "Type 1" are as shown in figures and .
•
If the positive directions of the winding 1 and winding 2 protection relay currents
equate, the
CT connection type
setting parameter is "Type 2". The connection
examples of "Type 2" are as shown in figures and .
•
The default value of the
CT connection type
setting is "Type 1".
•
If the positive directions of the winding 1 and winding 2 protection relay currents are
opposite, the
CT connection type
setting parameter is "Type 1". The connection
examples of "Type 1" are as shown in figures
.
•
If the positive directions of the winding 1 and winding 2 protection relay currents
equate, the
CT connection type
setting parameter is "Type 2". The connection
examples of "Type 2" are as shown in figures
.
•
The default value of the
CT connection type
setting is "Type 1".
In case the groundings of the current transformers on the phase side and the neutral side
are both either inside or outside the area to be protected, the setting parameter
CT
connection type
is "Type 1".
If the grounding of the current transformers on the phase side is inside the area to be
protected and the neutral side is outside the area to be protected or if the grounding on the
phase side is outside the area and on the neutral side inside the area, the setting parameter
CT connection type
is "Type 2".
1MAC059074-MB A
Section 4
Protection functions
615 series ANSI
543
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......