4.5.8.8
Monitored data
Table 578:
78V Monitored data
Name
Type
Values (Range)
Unit
Description
VEC_SHT_A_AB
FLOAT32
-180.00...180.00
deg
Vector shift for phase to
ground voltage A or phase to
phase voltage AB
VEC_SHT_B_BC
FLOAT32
-180.00...180.00
deg
Vector shift for phase to
ground voltage B or phase to
phase voltage BC
VEC_SHT_C_CA
FLOAT32
-180.00...180.00
deg
Vector shift for phase to
ground voltage C or phase to
phase voltage CA
VEC_SHT_U1
FLOAT32
-180.00...180.00
deg
Vector shift for positive
sequence voltage
78V
Enum
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
4.5.8.9
Technical data
Table 579:
78V Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured
voltage:
f
n
±1 Hz
±1°
Trip time
1)2)
Typically 53 ms
1) f
n
= 50 Hz, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
4.5.9
Three-phase remnant undervoltage protection 27R
4.5.9.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Three-phase remnant undervoltage
protection
MSVPR
3U<
27R
Section 4
1MAC059074-MB A
Protection functions
672
615 series ANSI
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......