Table 613:
Voltages and currents used in impedance calculation
Impedance Meas mode
Phase Sel for Z Clc
Voltages and currents used in
impedance calculation
1)
1Phase-phase
AB
ZAB
V AB
I A I B
=
−
_
_
_
1Phase-phase
BC
ZBC
V BC
I B I C
=
−
_
_
_
1Phase-phase
CA
ZCA
V CA
I C I A
=
−
_
_
_
3Phase-phase
N/A
ZAB
V AB
I A I B
=
−
_
_
_
ZBC
V BC
I B I C
=
−
_
_
_
ZCA
V CA
I C I A
=
−
_
_
_
1) Voltages and currents in the calculations are given in volts and amps.
If all three phase or phase-phase voltages and phase currents are fed to the
protection relay, the "3Phase-phase" mode is recommended.
The current measurement of the function is based on two alternative measurement modes,
"DFT" and "Peak-To-Peak". The measurement mode is selected using the
Measurement
mode
setting.
If the current magnitude is below 0.02 · I
N
, where I
N
is the nominal phase current, the
impedance value is not evaluated and the maximum impedance value (99.999 pu) is
shown in the Monitored data view.
The calculated impedances are converted to a pu impedance as the
operating characteristics are defined using the
Polar reach
setting in %Zb.
The calculated phase-phase impedance amplitudes ZAB_AMPL, ZBC_AMPL and
ZCA_AMPL are available as pu values in the Monitored data view.
Section 4
1MAC059074-MB A
Protection functions
708
615 series ANSI
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......