Voltage control mode
In the Voltage control mode, the Effective pickup value is calculated based on the
magnitude of input voltages
V_AB
,
V_BC
and
V_CA
. The voltage dependency is phase
sensitive, which means that the magnitude of one input voltage controls the pickup value
of only the corresponding phase, that is, the magnitude of voltage inputs
V_AB
,
V_BC
and
V_CA
independently control the current pickup values of phases A, B and C.
Two voltage control characteristics, voltage step and voltage slope, can be achieved with
the
Voltage high limit
and
Voltage low limit
settings.
The voltage step characteristic is achieved when the
Voltage high limit
setting is equal to
the
Voltage low limit
setting. The effective pickup value is calculated based on the
equations.
Voltage level
Effective pickup value (I> effective)
V <
Voltage high limit
Pickup value low
V ≥
Voltage high limit
Pickup value
In this example, V represents the measured input voltage. This voltage step characteristic
is graphically represented in
Figure
.
Pickup value low
Voltage high limit =
Voltage low limit
Pickup value
V
Effective
pickup value
GUID-D4FB20C7-61E4-4BF0-9F3F-B86FE500FFAE V1 EN
Figure 128:
Effective pickup value for voltage step characteristic
Section 4
1MAC059074-MB A
Protection functions
260
615 series ANSI
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......