In case
Syncro check mode
is set to "Syncronous", the additional conditions must be
fulfilled.
•
In the synchronous mode, the closing is attempted so that the phase difference at
closing is close to zero.
•
The synchronous mode is only possible when the frequency slip is below 0.1 percent
of the value of f
n
.
•
The voltage difference must not exceed the 1 percent of the value of V
n
.
In case
Syncro check mode
is set to “Asyncronous”, the additional conditions must be
fulfilled.
•
The measured difference of the voltages is less than the set value of
Difference
voltage
.
•
The measured difference of the phase angles is less than the set value of
Difference
angle
.
•
The measured difference in frequency is less than the set value of
Frequency
difference
.
•
The estimated breaker closing angle is decided to be less than the set value of
Difference angle
.
Dead line or bus value
Live line or bus value
Difference angle
V_Bus
V_Line
Difference voltage
f
V_Bus
f
V_Line
Frequency[Hz]
f
=
f
V_Bus
-
f
V_Line
Rated frequency
Frequency deviation
=
V_Bus
-
V_Line
Difference frequency
GUID-72527DBF-2FC1-4E3B-BE9D-E5978DB3BDA4 V2 EN
Figure 493:
Conditions to be fulfilled when detecting synchronism between systems
When the frequency, phase angle and voltage conditions are fulfilled, the duration of the
synchronism conditions is checked so as to ensure that they are still met when the
condition is determined on the basis of the measured frequency and phase difference.
Depending on the circuit breaker and the closing system, the delay from the moment the
closing signal is given until the circuit breaker finally closes is about 50...250 ms. The
selected
Closing time of CB
informs the function how long the conditions have to persist.
The Synchro check function compensates for the measured slip frequency and the circuit
1MAC059074-MB A
Section 9
Control functions
615 series ANSI
979
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......