Voltage swell set 3
Voltage swell set 2
Voltage swell set 1
Voltage
xVref
Time (ms)
0
0
VVa Dur Max
VVa swell time 3
VVa swell time 1
VVa swell time 2
1.40
Instantaneous
swell
Temporary
swell
Momentary
swell
Maximum duration
swell
1.00
GUID-C1C6BEEF-439A-4DF7-8065-5F88C7517834-ANSI V1 EN
Figure 533:
Voltage swell operational regions
, there is only one magnitude limit but four
duration limits for interruption classification. Now the event and counter type depends
only on variation duration time.
Voltage Int set
Voltage
xVref
Time (ms)
0
0
VVa Dur Max
VVa Int time 3
VVa Int time 1
VVa Int time 2
1.00
Momentary
interruption
Sustained
interruption
Temporary
interruption
Maximum duration
interruption
GUID-0204C8EA-102C-4327-BE84-DCE27747AA30-ANSI V1 EN
Figure 534:
Interruption operating regions
Generally, no event detection is done if both the magnitude and duration requirements are
not fulfilled. For example, the dip event does not indicate if the TRMS voltage magnitude
remains between
Voltage dip set 3
and
Voltage dip set 2
for a period shorter than
VVa dip
time 3
before rising back above
Voltage dip set 3
.
Section 10
1MAC059074-MB A
Power quality measurement functions
1046
615 series ANSI
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......