Table 857:
84T Output signals
Name
Type
Description
TAP_POS
INT8
Tap position indication
8.3.7
Settings
Table 858:
84T Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=enable
5=disable
1=enable
Operation Disable / Enable
Operation mode
1=NAT2INT
2=BCD2INT
3=GRAY2INT
2=BCD2INT
Operation mode selection
8.3.8
Monitored data
Table 859:
84T Monitored data
Name
Type
Values (Range)
Unit
Description
BI0
BOOLEAN
0=False
1=True
Binary input 1
BI1
BOOLEAN
0=False
1=True
Binary input 2
BI2
BOOLEAN
0=False
1=True
Binary input 3
BI3
BOOLEAN
0=False
1=True
Binary input 4
BI4
BOOLEAN
0=False
1=True
Binary input 5
BI5
BOOLEAN
0=False
1=True
Binary input 6
SIGN_BIT
BOOLEAN
0=False
1=True
Binary input sign bit
END_POS_R
BOOLEAN
0=False
1=True
End position raise or highest
allowed tap position reached
END_POS_L
BOOLEAN
0=False
1=True
End position lower or lowest
allowed tap position reached
TAP_POS
INT8
-63...63
Tap position indication
1MAC059074-MB A
Section 8
Measurement functions
615 series ANSI
955
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......