output is set for a specific duration using the
Pulse time
setting. Both timers use the same
setting parameter.
GUID-9BE17BA5-70D3-442B-8D24-8544C7A9441A V1 EN
Figure 81:
A = Trip pulse is shorter than Cold load time setting, B = Trip pulse is
longer than Cold load time setting
Signals
Table 149:
62TPM Input signals
Name
Type
Default
Description
IN1
BOOLEAN
0=False
Input 1
IN2
BOOLEAN
0=False
Input 2
Table 150:
62TPM Output signals
Name
Type
Description
OUT1
BOOLEAN
Output 1 status
OUT2
BOOLEAN
Output 2 status
Settings
Table 151:
62TPM Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Cold load time
0...300
min
1
0
Cold load time
3.17.3
Pulse timer function block 62PT
3.17.3.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Pulse timer (8 pcs)
PTGAPC
PT
62PT
Section 3
1MAC059074-MB A
Basic functions
168
615 series ANSI
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......