Name
Type
Values (Range)
Unit
Description
U_3H_N
FLOAT32
0.00...40.00
xUn
Neutral side 3rd harmonic
voltage amplitude
U_3HANGL_T_N
FLOAT32
-180.00...180.00
deg
Phase angle between 3rd
harmonic terminal and neutral
voltage
27/59THN
Enum
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
4.2.7.9
Technical data
Table 414:
27/59THN Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured
voltage:
f
n
±2 Hz
±5% of the set value or ±0.004 × V
n
Pickup time
1)2)
Typically 35 ms
Reset time
Typically 35 ms
Reset ratio
Typically 0.96 (differential mode)
Typically 1.04 (under voltage mode)
Trip time accuracy
±1.0% of the set value of ±20 ms
1) f
n
= 50 Hz, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
4.2.8
Multifrequency admittance-based ground-fault protection 67YN
4.2.8.1
Identification
Description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Multifrequency admittance-based
ground-fault protection
MFADPSDE
Io> ->Y
67YN
1MAC059074-MB A
Section 4
Protection functions
615 series ANSI
437
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......