Name
Type
Values (Range)
Unit
Description
CNT_SHOT2
INT32
0...2147483647
Resetable operation counter,
shot 2
CNT_SHOT3
INT32
0...2147483647
Resetable operation counter,
shot 3
CNT_SHOT4
INT32
0...2147483647
Resetable operation counter,
shot 4
CNT_SHOT5
INT32
0...2147483647
Resetable operation counter,
shot 5
COUNTER
INT32
0...2147483647
Resetable operation counter,
all shots
SHOT_PTR
INT32
1...7
Shot pointer value
MAN_CB_CL
BOOLEAN
0=False
1=True
Indicates CB manual closing
during reclosing sequence
SOTF
BOOLEAN
0=False
1=True
Switch-onto-fault
79
Enum
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
9.4.10
Technical data
Table 913:
79 Technical data
Characteristic
Value
Trip time accuracy
±1.0% of the set value or ±20 ms
9.4.11
Technical revision history
Table 914:
79 Technical revision history
Technical revision
Change
B
The
PROT_DISA
output removed and removed the
related settings
C
The default value of the
CB closed Pos status setting
changed from "True" to "False"
D
SHOT_PTR output range 0...7 (earlier 0...6)
E
Monitored data ACTIVE transferred to be ACT visible
output. SHOT_PTR output range 1...7.
F
Internal improvement
1MAC059074-MB A
Section 9
Control functions
615 series ANSI
1031
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......