Parameter
Values (Range)
Unit
Step
Default
Description
Pressure alarm time
0...60000
ms
1
10
Time delay for gas pressure alarm in ms
Pres lockout time
0...60000
ms
10
10
Time delay for gas pressure lockout in ms
Ini inactive days
0...9999
1
0
Initial value of the inactive days counter
Inactive Alm hours
0...23
h
1
0
Alarm time of the inactive days counter in hours
7.1.8
Monitored data
Table 787:
52CM Monitored data
Name
Type
Values (Range)
Unit
Description
T_TRV_OP
FLOAT32
0...60000
ms
Travel time of the CB during
opening operation
T_TRV_CL
FLOAT32
0...60000
ms
Travel time of the CB during
closing operation
T_SPR_CHR
FLOAT32
0.00...99.99
s
The charging time of the CB
spring
NO_OPR
INT32
0...99999
Number of CB operation cycle
INA_DAYS
INT32
0...9999
The number of days CB has
been inactive
CB_LIFE_A
INT32
-99999...99999
CB Remaining life phase A
CB_LIFE_B
INT32
-99999...99999
CB Remaining life phase B
CB_LIFE_C
INT32
-99999...99999
CB Remaining life phase C
IPOW_A
FLOAT32
0.000...30000.00
0
Accumulated currents power
(Iyt), phase A
IPOW_B
FLOAT32
0.000...30000.00
0
Accumulated currents power
(Iyt), phase B
IPOW_C
FLOAT32
0.000...30000.00
0
Accumulated currents power
(Iyt), phase C
52CM
Enum
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
1MAC059074-MB A
Section 7
Condition monitoring functions
615 series ANSI
895
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......