X130
+
-
1
2
8
Transducer
Sensor
Shunt
(44
Ω
)
...
...
...
GUID-FBB50B49-0EFE-4D1C-AB71-204C3E170C1D V2 EN
Figure 41:
mA wiring connection for RTD/mA card
3.13.3
Signals
Table 57:
RTD Output signals
Name
Type
Description
ALARM
BOOLEAN
General alarm
WARNING
BOOLEAN
General warning
AI_VAL1
FLOAT32
mA input, Connectors 1-2, instantaneous value
AI_VAL2
FLOAT32
mA input, Connectors 3-4, instantaneous value
AI_VAL3
FLOAT32
RTD input, Connectors 5-6-11c, instantaneous value
AI_VAL4
FLOAT32
RTD input, Connectors 7-8-11c, instantaneous value
AI_VAL5
FLOAT32
RTD input, Connectors 9-10-11c, instantaneous value
AI_VAL6
FLOAT32
RTD input, Connectors 13-14-12c, instantaneous value
AI_VAL7
FLOAT32
RTD input, Connectors 15-16-12c, instantaneous value
AI_VAL8
FLOAT32
RTD input, Connectors 17-18-12c, instantaneous value