![background image](http://html.mh-extra.com/html/abb/relion-615-series/relion-615-series_technical-manual_2395827.webp)
Table 715:
Impedance settings
Parameter
Impedance model with one section Impedance model with three
sections
R1 line section A
0.660 Ω/pu
0.236 Ω/pu
X1 line section A
0.341 Ω/pu
0.276 Ω/pu
Line Len section A
10000 pu
4000 pu
R1 line section B
N/A
0.536 Ω/pu
X1 line section B
N/A
0.369 Ω/pu
Line Len section B
0.000 pu
3000 pu
R1 line section C
N/A
1.350 Ω/pu
X1 line section C
N/A
0.398 Ω/pu
Line Len section C
0.000 pu
3000 pu
illustrates the conversion error from measured fault loop reactance into
physical fault distance. The fault location is varied from 1 km to 10 km in 1 km steps
(marked with circles). An error of nearly eight per cent at maximum is created by the
conversion procedure when modeling a non-homogenous line with only one section. By
using impedance model with three line sections, there is no error in the conversion.
The previous example assumed a short circuit fault and thus, only positive-sequence
impedance settings were used. The results, however, also apply for ground faults.
Taps or spurs in the feeder
If the protected feeder consists of taps or spurs, the measured fault impedance corresponds
to several physical fault locations (For example, A or B in
location must be identified using additional information, for example, short circuit current
indicators placed on tapping points.
1MAC059074-MB A
Section 5
Protection related functions
615 series ANSI
821
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......