of 1.0 × In corresponds to 1.0 * 100 A = 100 A in the primary. The
Voltage pickup value
of 1.0 × Vn corresponds to 1.0 * 11.547 kV = 11.547 kV in the primary.
Example 2
: Both I0 and V0 are calculated from the phase quantities. Phase CT-ratio is
100 : 1 A and phase VT-ratio is 20/sqrt(3) kV : 100/sqrt(3) V. In this case, "Calculated I0"
and "Calculated V0" are selected. The nominal values for residual current and residual
voltage are obtained from CT and VT ratios entered in Residual current I0:
Configuration/Analog inputs/Current (3I,CT)
: 100 A : 1 A. The residual voltage V0:
Configuration/Analog inputs/Voltage (3V,VT)
: 20.000 kV : 100 V. The
Pickup value
of 1.0 × In corresponds to 1.0 * 100 A = 100 A in the primary. The
Voltage pickup value
of 1.0 × Vn corresponds to 1.0 * 20.000 kV = 20.000 kV in the primary.
If "Calculated V0" is selected, the residual voltage nominal value is
always phase-to-phase voltage. Thus, the valid maximum setting for
residual Voltage pickup value is 0.577 x Vn. The calculated V0 requires
that all the three phase-to-ground voltages are connected to the protection
relay. V0 cannot be calculated from the phase-to-phase voltages.
If the
Enable voltage limit
setting is set to "True", the magnitude of the
polarizing quantity is checked even if the
Directional mode
was set to
"Non-directional" or
Allow Non Dir
to "True". The protection relay does
not accept the
Pickup value
or
Pickup value Mult
setting if the product of
these settings exceeds the
Pickup value
setting range.
Typically, the
ENA_MULT
input is connected to the inrush detection function INR. In case
of inrush, INR activates the
ENA_MULT
input, which multiplies
Pickup value
by the
Pickup value Mult
setting.
Directional calculation
The directional calculation module monitors the angle between the polarizing quantity
and operating quantity. Depending on the
Pol quantity
setting, the polarizing quantity can
be the residual voltage (measured or calculated) or the negative sequence voltage. When
the angle is in the operation sector, the module sends the enabling signal to the timer
module.
The minimum signal level which allows the directional operation can be set with the
Min
trip current
and
Min trip voltage
settings.
If
Pol quantity
is set to "Zero. seq. volt", the residual current and residual voltage are used
for directional calculation.
If
Pol quantity
is set to "Neg. seq. volt", the negative sequence current and negative
sequence voltage are used for directional calculation.
Section 4
1MAC059074-MB A
Protection functions
328
615 series ANSI
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......