Table 302:
37 Output signals
Name
Type
Description
TRIP
BOOLEAN
Trip
TRIP_A
BOOLEAN
Trip phase A
TRIP_B
BOOLEAN
Trip phase B
TRIP_C
BOOLEAN
Trip phase C
PICKUP
BOOLEAN
Pickup
PICKUP_A
BOOLEAN
Pickup phase A
PICKUP_B
BOOLEAN
Pickup phase B
PICKUP_C
BOOLEAN
Pickup phase C
4.1.8.7
Settings
Table 303:
37 Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Current block value
0.00...0.50
xIn
0.01
0.10
Low current setting to block internally
Pickup value
0.01...1.00
xIn
0.01
0.50
Current setting to pickup
Trip delay time
50...200000
ms
10
2000
Trip delay time
Table 304:
37 Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=enable
5=disable
1=enable
Operation Disable / Enable
Operation mode
1=Three Phase
2=Single Phase
1=Three Phase
Number of phases needed to pickup
Table 305:
37 Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reset delay time
0...60000
ms
1
20
Reset delay time
Section 4
1MAC059074-MB A
Protection functions
296
615 series ANSI
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......