4.8.2.7
Settings
Table 632:
32R/32O Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Pickup value
0.01...2.00
xSn
0.01
1.00
Pickup value
Trip delay time
40...300000
ms
10
40
Trip delay time
Directional mode
2=Forward
3=Reverse
2=Forward
Directional mode
Power angle
-90...90
deg
1
0
Adjustable angle for power
Table 633:
32R/32O Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=enable
5=disable
1=enable
Operation Disable / Enable
Measurement mode
1=PhsA, PhsB,
PhsC
2=Arone
3=Pos Seq
4=PhsAB
5=PhsBC
6=PhsCA
7=PhsA
8=PhsB
9=PhsC
3=Pos Seq
Selection of power calculation method
Table 634:
32R/32O Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reset delay time
0...60000
ms
10
20
Reset delay time
Pol reversal
0=False
1=True
0=False
Reverse the definition of the power direction
4.8.2.8
Monitored data
Table 635:
32R/32O Monitored data
Name
Type
Values (Range)
Unit
Description
PICKUP_DUR
FLOAT32
0.00...100.00
%
Ratio of pickup time / trip time
P
FLOAT32
-160.000...160.0
00
xSn
Active power
Q
FLOAT32
-160.000...160.0
00
xSn
Reactive power
Table continues on next page
Section 4
1MAC059074-MB A
Protection functions
732
615 series ANSI
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......