Timer 1
Once activated, the timer runs until the set
Retrip time
value has elapsed. The time
characteristic is according to DT. When the operation timer has reached the value set with
Retrip time
, the retrip logic is activated. A typical setting is 0...50 ms.
Timer 2
Once activated, the timer runs until the set
CB failure delay
value has elapsed. The time
characteristic is according to DT. When the operation timer has reached the set maximum
time value
CB failure delay
, the backup trip logic is activated. The value of this setting is
made as low as possible at the same time as any unwanted operation is avoided. A typical
setting is 90 - 150 ms, which is also dependent on the retrip timer.
The minimum time delay for the CB failure delay can be estimated as:
CBfailuredelay
Retriptime
t
t
t
cbopen
BFP reset
margin
≥
+
+
+
_
A070693 V3 EN
(Equation 136)
t
cbopen
maximum opening time for the circuit breaker
t
BFP_reset
maximum time for the breaker failure protection to detect the correct breaker function (the current
criteria reset)
t
margin
safety margin
It is often required that the total fault clearance time is less than the given critical time. This
time often depends on the ability to maintain transient stability in case of a fault close to
a power plant.
Section 5
1MAC059074-MB A
Protection related functions
776
615 series ANSI
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......