Re(Yo)
Im(Yo)
Conductance
forward
Conductance
tilt
Ang
<0
Re(Yo)
Im(Yo)
Conductance
tilt
Ang
>0
Re(Yo)
Im(Yo)
TRIP
TRIP
TRIP
TRIP
TRIP
TRIP
Conductance
forward
Conductance
forward
GUID-3D218EC0-4681-471D-B279-52D7810C1A24 V1 EN
Figure 183:
Forward directional overconductance characteristic. Left figure: classical
forward directional overconductance criterion. Middle figure:
characteristic is tilted with negative tilt angle. Right figure: characteristic
is tilted with positive tilt angle.
Forward directional oversusceptance characteristic
The forward directional oversusceptance criterion is enabled with the
Operation mode
setting set to "Bo" and
Directional mode
to "Forward". The characteristic is defined by
one oversusceptance boundary line with the
Susceptance forward
setting. For the sake of
application flexibility, the boundary line can be tilted by the angle defined with the
Susceptance tilt Ang
setting. By default, the tilt angle is zero degrees, that is, the boundary
line is a horizontal line in the admittance plane. A positive tilt value rotates the boundary
line counterclockwise from the horizontal axis.
Operation is achieved when the measured admittance moves over the boundary line.
The forward directional oversusceptance criterion is applicable in
ungrounded networks. It must not be applied to compensated networks.
1MAC059074-MB A
Section 4
Protection functions
615 series ANSI
389
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......