Table 967:
X12 Optical ST connection
Group
Jumper connection
Description
X3
1-2
2-3
Star topology
Loop topology
X24
1-2
2-3
Idle state = Light on
Idle state = Light off
Table 968:
EIA-232 connections for COM0023 (X6)
Pin
EIA-232
1
DCD
2
RxD
3
TxD
4
DTR
5
AGND
6
-
7
RTS
8
CTS
Table 969:
EIA-485 connections for COM0023 (X6)
Pin
2-wire mode
4-wire mode
1
-
Rx/+
6
-
Rx/-
7
B/-
Tx/-
8
A/+
Tx/+
Table 970:
EIA-485 connections for COM0023 (X5)
Pin
2-wire mode
4-wire mode
9
-
Rx/+
8
-
Rx/-
7
A/+
Tx/+
6
B/-
Tx/-
5
AGND (isolated ground)
4
IRIG-B +
3
IRIG-B -
2
-
1
GND (case)
1MAC059074-MB A