4.5.3.7
Settings
Table 534:
59N,59G Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Pickup value
0.010...1.000
xUn
0.001
0.030
Pickup value
Trip delay time
40...300000
ms
1
40
Trip delay time
Table 535:
59N,59G Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=enable
5=disable
1=enable
Operation Disable / Enable
VG/V0 Select
1=Measured VG
2=Calculated V0
1=Measured VG
Selection for used VG/V0 signal
Table 536:
59N,59G Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reset delay time
0...60000
ms
1
20
Reset delay time
4.5.3.8
Monitored data
Table 537:
59N,59G Monitored data
Name
Type
Values (Range)
Unit
Description
PICKUP_DUR
FLOAT32
0.00...100.00
%
Ratio of pickup time / trip time
59N,59G
Enum
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
4.5.3.9
Technical data
Table 538:
59N, 59G Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured
voltage: f
n
±2 Hz
±1.5% of the set value or ±0.002 × V
n
Pickup time
1)2)
Minimum
Typical
Maximum
V
Fault
= 2 × set
Pickup
value
48 ms
51 ms
54 ms
Table continues on next page
1MAC059074-MB A
Section 4
Protection functions
615 series ANSI
631
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......