3.5.1.4
Settings
Table 29:
Time format
Parameter
Values (Range)
Unit
Step
Default
Description
Time format
1=24H:MM:SS:MS
2=12H:MM:SS:MS
1=24H:MM:SS:M
S
Time format
Date format
1=DD.MM.YYYY
2=DD/MM/YYYY
3=DD-MM-YYYY
4=MM.DD.YYYY
5=MM/DD/YYYY
6=YYYY-MM-DD
7=YYYY-DD-MM
8=YYYY/DD/MM
1=DD.MM.YYYY
Date format
Table 30:
Time settings
Parameter
Values (Range)
Unit
Step
Default
Description
Synch source
0=None
1=SNTP
2=Modbus
3=IEEE 1588
5=IRIG-B
9=DNP
1=SNTP
Time synchronization source
PTP domain ID
0...255
1
0
The domain is identified by an integer, the
domainNumber, in the range of 0 to 255.
PTP priority 1
0...255
1
128
PTP priority 1, in the range of 0 to 255.
PTP priority 2
0...255
1
128
PTP priority 2, in the range of 0 to 255.
PTP announce mode
1=Basic IEEE1588
2=Power Profile
1=Basic IEEE1588 PTP announce frame mode
Table 31:
Time settings
Parameter
Values (Range)
Unit
Step
Default
Description
Date
0
Date
Time
0
Time
Local time offset
-840...840
min
1
0
Local time offset in minutes
Table 32:
Time settings
Parameter
Values (Range)
Unit
Step
Default
Description
IP SNTP primary
10.58.125.165
IP address for SNTP primary server
IP SNTP secondary
192.168.2.165
IP address for SNTP secondary server
1MAC059074-MB A
Section 3
Basic functions
615 series ANSI
85
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......