3.14.1.2
Functionality
The SMVSENDER function block is used for activating the SMV sending functionality.
It adds/removes the sampled value control block and the related data set into/from the
sending device's configuration. It has no input or output signals.
SMVSENDER can be disabled with the
Operation
setting value “off”. If the
SMVSENDER is disabled from the LHMI, it can only be enabled from the LHMI. When
disabled, the sending of the samples values is disabled.
3.14.1.3
Settings
Table 61:
SMVSENDER Settings
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation
3.14.2
IEC 61850-9-2 LE sampled values receiving SMVRECEIVER
3.14.2.1
Function block
UL1
SMVRECEIVER
UL2
UL3
Uo
GUID-EB0B6F8A-724A-4090-A94B-0BD935BB03F4 V1 EN
Figure 43:
Function block
3.14.2.2
Functionality
The SMVRECEIVER function block is used for activating the SMV receiving
functionality.
3.14.2.3
Signals
Table 62:
SMVRECEIVER Output signals
Name
Type
Description
UL1
INT32-UL1
IEC61850-9-2 phase 1 voltage
UL2
INT32-UL2
IEC61850-9-2 phase 2 voltage
UL3
INT32-UL3
IEC61850-9-2 phase 3 voltage
U0
INT32-Uo
IEC61850-9-2 residual voltage
Section 3
1MAC059074-MB A
Basic functions
130
615 series ANSI
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......