a low level limit violation, if the measured value falls below approximately 0.05 during
the filter time, the situation is considered to be a circuit-breaker operation and therefore,
the recorder does not trigger. This is useful especially in undervoltage situations. The filter
time of approximately 50 ms is common to all the analog channel triggers of the
disturbance recorder. The value used for triggering is the calculated peak-to-peak value.
Either high or low analog channel trigger can be disabled by setting the corresponding
trigger level parameter to zero.
Manual triggering
The recorder can be triggered manually via the LHMI or via communication by setting the
Trig recording
parameter to TRUE.
Periodic triggering
Periodic triggering means that the recorder automatically makes a recording at certain
time intervals. The user can adjust the interval with the
Periodic trig time
parameter. If the
value of the parameter is changed, the new setting takes effect when the next periodic
triggering occurs. Setting the parameter to zero disables the triggering alternative and the
setting becomes valid immediately. If a new non-zero setting needs to be valid
immediately, the user should first set the
Periodic trig time
parameter to zero and then to
the new value. The user can monitor the time remaining to the next triggering with the
Time to trigger
monitored data which counts downwards.
8.2.2.3
Length of recordings
The user can define the length of a recording with the
Record length
parameter. The length
is given as the number of fundamental cycles.
According to the memory available and the number of analog channels used, the
disturbance recorder automatically calculates the remaining amount of recordings that fit
into the available recording memory. The user can see this information with the
Rem.
amount of rec
monitored data. The fixed memory size allocated for the recorder can
fit in two recordings that are ten seconds long. The recordings contain data from all analog
and binary channels of the disturbance recorder, at the sample rate of 32 samples per
fundamental cycle.
The user can view the number of recordings currently in memory with the
Number of
recordings
monitored data. The currently used memory space can be viewed with the
Rec. memory used
monitored data. It is shown as a percentage value.
The maximum number of recordings is 100.
1MAC059074-MB A
Section 8
Measurement functions
615 series ANSI
939
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......