input activated
Phase selection logic
If the fault criteria are fulfilled in the level detector, the phase selection logic detects the
phase or phases in which the measured current exceeds the setting. If the phase
information matches the
Num of pickup phases
setting, the phase selection logic activates
the timer module.
Timer
Once activated, the timer activates the
PICKUP
output. Depending on the value of the
Operating curve type
setting, the time characteristics are according to DT or IDMT. When
the operation timer has reached the value of
Trip delay time
in the DT mode or the
maximum value defined by the inverse time curve, the
TRIP
output is activated.
When the user-programmable IDMT curve is selected, the operation time characteristics
are defined by the parameters
Curve parameter A
,
Curve parameter B
,
Curve parameter
C
,
Curve parameter D
and
Curve parameter E
.
If a drop-off situation happens, that is, a fault suddenly disappears before the trip delay is
exceeded, the timer reset state is activated. The functionality of the timer in the reset state
depends on the combination of the
Operating curve type
,
Type of reset curve
and
Reset
delay time
settings. When the DT characteristic is selected, the reset timer runs until the set
1MAC059074-MB A
Section 4
Protection functions
615 series ANSI
213
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......