This CB mode can be used in soft-started or slip ring motors for protection against a large
starting current, that is, a problem in starting and so on.
GUID-DDAD7B3F-28BE-4573-BE79-FBB488A22ECA V1 EN
GUID-1470A4DB-310F-46BC-B775-843EAB8BA836 V1 EN
Figure 378:
Functionality of start-up supervision in the "IIt, CB" mode and the "IIt and
stall, CB" mode
The
Str over delay time
setting has different purposes in different modes of operation.
•
In the “IIt” or “IIt & stall” modes, the aim of this setting is to check for the completion
of the motor start-up period. The purpose of this time delay setting is to allow for short
interruptions in the current without changing the state of the
MOT_START
output. In
1MAC059074-MB A
Section 4
Protection functions
615 series ANSI
753
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......