Table 625:
32U Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=enable
5=disable
1=enable
Operation Disable / Enable
Table 626:
32U Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Measurement mode
1=PhsA, PhsB,
PhsC
2=Arone
3=Pos Seq
4=PhsAB
5=PhsBC
6=PhsCA
7=PhsA
8=PhsB
9=PhsC
3=Pos Seq
Selection of power calculation method
Reset delay time
0...60000
ms
10
20
Reset delay time
Pol reversal
0=False
1=True
0=False
Reverse the definition of the power direction
Disable time
0...60000
ms
1000
0
Additional wait time after CB closing
4.8.1.8
Monitored data
Table 627:
32U Monitored data
Name
Type
Values (Range)
Unit
Description
PICKUP_DUR
FLOAT32
0.00...100.00
%
Ratio of pickup time / trip time
P
FLOAT32
-160.000...160.0
00
xSn
Active power
Q
FLOAT32
-160.000...160.0
00
xSn
Reactive power
S
FLOAT32
0.000...160.000
xSn
Apparent power
PF_ANGLE
FLOAT32
-180.00...180.00
deg
Power factor angle
32U
Enum
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
1MAC059074-MB A
Section 4
Protection functions
615 series ANSI
723
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......