Name
Type
Values (Range)
Unit
Description
ANGLE_RCA
FLOAT32
-180.00...180.00
deg
Angle between polarizing and
operating quantity
ANGLE
FLOAT32
-180.00...180.00
deg
Angle between operating
angle and characteristic angle
I_OPER
FLOAT32
0.00...40.00
xIn
Calculated operating current
67/51N
Enum
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
Table 366:
67/50N Monitored data
Name
Type
Values (Range)
Unit
Description
FAULT_DIR
Enum
0=unknown
1=forward
2=backward
3=both
Detected fault direction
PICKUP_DUR
FLOAT32
0.00...100.00
%
Ratio of pickup time / trip time
DIRECTION
Enum
0=unknown
1=forward
2=backward
3=both
Direction information
ANGLE_RCA
FLOAT32
-180.00...180.00
deg
Angle between polarizing and
operating quantity
ANGLE
FLOAT32
-180.00...180.00
deg
Angle between operating
angle and characteristic angle
I_OPER
FLOAT32
0.00...40.00
xIn
Calculated operating current
67/50N
Enum
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
Section 4
1MAC059074-MB A
Protection functions
358
615 series ANSI
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......