Table 802:
VA,VB,VC Output signals
Name
Type
Description
HIGH_ALARM
BOOLEAN
High alarm
HIGH_WARN
BOOLEAN
High warning
LOW_WARN
BOOLEAN
Low warning
LOW_ALARM
BOOLEAN
Low alarm
8.1.5.4
Settings
Table 803:
VA,VB,VC Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=enable
5=disable
1=enable
Operation Disable / Enable
Num of phases
1=1 out of 3
2=2 out of 3
3=3 out of 3
1=1 out of 3
Number of phases required by limit supervision
V high high limit
0.00...4.00
xUn
1
1.40
High alarm voltage limit
V high limit
0.00...4.00
xUn
1
1.20
High warning voltage limit
V low limit
0.00...4.00
xUn
1
0.00
Low warning voltage limit
V low low limit
0.00...4.00
xUn
1
0.00
Low alarm voltage limit
V deadband
100...100000
1
10000
Deadband configuration value for integral
calculation. (percentage of difference between
min and max as 0,001 % s)
Table 804:
VA,VB,VC Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Measurement mode
1=RMS
2=DFT
2=DFT
Selects used measurement mode
8.1.5.5
Monitored data
Table 805:
VA,VB,VC Monitored data
Name
Type
Values (Range)
Unit
Description
VAB-kV
FLOAT32
0.00...4.00
xUn
Measured phase to phase
voltage amplitude phase AB
VBC-kV
FLOAT32
0.00...4.00
xUn
Measured phase to phase
voltage amplitude phase BC
VCA-kV
FLOAT32
0.00...4.00
xUn
Measured phase to phase
voltage amplitude phase CA
Table continues on next page
1MAC059074-MB A
Section 8
Measurement functions
615 series ANSI
911
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......