4.5
Voltage protection
4.5.1
Three-phase overvoltage protection 59
4.5.1.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Three-phase overvoltage protection
PHPTOV
3U>
59
4.5.1.2
Function block
A070122 V2 EN
Figure 307:
Function block
4.5.1.3
Functionality
The three-phase overvoltage protection function 59 is applied on power system elements,
such as generators, transformers, motors and power lines, to protect the system from
excessive voltages that could damage the insulation and cause insulation breakdown. The
three-phase overvoltage function includes a settable value for the detection of overvoltage
either in a single phase, two phases or three phases.
59 includes both definite time (DT) and inverse definite minimum time (IDMT)
characteristics for the delay of the trip.
The function contains a blocking functionality. It is possible to block function outputs,
timer or the function itself, if desired.
4.5.1.4
Operation principle
The function can be enabled and disabled with the
Operation
setting. The corresponding
parameter values are “Enable” and “Disable”.
The operation of 59 can be described using a module diagram. All the modules in the
diagram are explained in the next sections.
Section 4
1MAC059074-MB A
Protection functions
610
615 series ANSI
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......