Name
Type
Default
Description
BLOCK
BOOLEAN
0=False
Block signal for all binary outputs
REM_FLT_ARC
BOOLEAN
0=False
Remote Fault arc detected
OPR_MODE
BOOLEAN
0=False
Operation mode input
Table 645:
AFD Output signals
Name
Type
Description
TRIP
BOOLEAN
Trip
ARC_FLT_DET
BOOLEAN
Fault arc detected=light signal output
4.9.7
Settings
Table 646:
AFD Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Phase pickup value
0.50...40.00
xIn
0.01
2.50
Operating phase current
Ground pickup value
0.05...8.00
xIn
0.01
0.20
Operating residual current
Operation mode
1=Light+current
2=Light only
3=BI controlled
1=Light+current
Operation mode
Table 647:
AFD Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=enable
5=disable
1=enable
Operation Disable / Enable
4.9.8
Monitored data
Table 648:
AFD Monitored data
Name
Type
Values (Range)
Unit
Description
AFD
Enum
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
Section 4
1MAC059074-MB A
Protection functions
748
615 series ANSI
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......