Phase angle 88
The operation criterion phase angle 88 is selected with the
Operation mode
setting using
the value "Phase angle 88".
Phase angle 88 implements the same functionality as the phase angle but with the
following differences:
•
The
Max forward angle
and
Max reverse angle
settings cannot be set but they have
a fixed value of 88 degrees
•
The sector limits of the fixed sectors are rounded.
Sector rounding in the phase angle 88 consists of three parts:
•
If the current amplitude is between 1...20 percent of the nominal current, the sector
limit increases linearly from 73 degrees to 85 degrees
•
If the current amplitude is between 20...100 percent of the nominal current, the sector
limit increases linearly from 85 degrees to 88 degrees
•
If the current amplitude is more than 100 percent of the nominal current, the sector
limit is 88 degrees.
There is no sector rounding on the other side of the sector.
Section 4
1MAC059074-MB A
Protection functions
348
615 series ANSI
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......