individual reset for each
Q#
output is available on the LHMI or through tool via
communication.
Table 164:
Truth table for SR
S#
R#
Q#
0
0
0
1)
0
1
0
1
0
1
1
1
1
1) Keep state/no change
3.17.6.4
Signals
Table 165:
SR Input signals
Name
Type
Default
Description
S1
BOOLEAN
0=False
Set Q1 output when set
R1
BOOLEAN
0=False
Resets Q1 output when set
S2
BOOLEAN
0=False
Set Q2 output when set
R2
BOOLEAN
0=False
Resets Q2 output when set
S3
BOOLEAN
0=False
Set Q3 output when set
R3
BOOLEAN
0=False
Resets Q3 output when set
S4
BOOLEAN
0=False
Set Q4 output when set
R4
BOOLEAN
0=False
Resets Q4 output when set
S5
BOOLEAN
0=False
Set Q5 output when set
R5
BOOLEAN
0=False
Resets Q5 output when set
S6
BOOLEAN
0=False
Set Q6 output when set
R6
BOOLEAN
0=False
Resets Q6 output when set
S7
BOOLEAN
0=False
Set Q7 output when set
R7
BOOLEAN
0=False
Resets Q7 output when set
S8
BOOLEAN
0=False
Set Q8 output when set
R8
BOOLEAN
0=False
Resets Q8 output when set
Table 166:
SR Output signals
Name
Type
Description
Q1
BOOLEAN
Q1 status
Q2
BOOLEAN
Q2 status
Q3
BOOLEAN
Q3 status
Table continues on next page
Section 3
1MAC059074-MB A
Basic functions
176
615 series ANSI
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......