background image

466-2338A • October 2009

© 2009 GE Security, Inc.

g

NX-6V2-Control Panel

Installation Instructions

Introduction

This is the GE 

NX-6V2-Control Panel Installation Instructions. 

Installations should only be done by trained professionals. 
Use this document to install the system with default settings 
that comply with UL requirements. 
To install the keypad, other peripherals, and sensors, refer to 
the documentation for those devices.

Installation

There are four slots for board insertions inside the metal 
enclosure, two on the top and two on the bottom. These allow 
the PC board to be positioned vertically (

Figure 1

). When you 

slide the board between the grooves of the slots, make sure 
the terminal strip is toward the front opening (toward you) to 
allow for the wire connections.

Note:  

Install the metal enclosure with the door opening from the top 

to bottom.

Figure 1. Board installation

NetworX keypad maximum wire run

Table 1

 lists wire lengths for one keypad at the end of the 

wire. When connecting more than one keypad to the end of 
the wire, a higher gauge wire is required. 

Terminal descriptions

Table 2

 describes the panel terminals.

Table 1.

Maximum keypad wire run

Length in feet

Wire gauge for NX-6V2

Wire gauge for NX320-E

250

24

22

500

20

18

1000

18

16

1500

16

14

2500

14

12

Table 2.

NX-6V2 terminals

Terminal

Description

R1

House telephone ring (grey).

R

Telephone ring (red).

T

Telephone tip (green).

T1

House telephone tip (brown).

EARTH

Earth ground. Connect to a cold water pipe or a 6 to 10 ft. 

driven rod.

AC

AC input. Connect to a 16.5 V, 40 or 50 VA Class II UL 

approved transformer.

Bell + and 

Bell -

If used as a siren output (default), the speaker rating should 

be 15 watt at 8 or 16 ohm, or 30/40 watt at 4, 8, or 16 ohms. If 

voltage ouput is selected in location 37, this output becomes 

voltage output, 12 VDC, 1 Amp maximum load. Note: A 3.3 

kohm resistor may be required across the bell terminals 

when a 12 VDC siren is used. If no resistor is used, you may 

experience voltage leakage into the siren, which will cause 

these devices to output a small signal.

KP DATA

Connect to the data terminal on the keypads and the 

expanders. Maximum number of devices is 16 keypads plus 3 

other de vices. See Maximum Wire Run table. 

KP COM

Connect to the common terminal on the keypads and the 

expanders.

KP POS

Connect to the POS terminal on the keypads and the 

expanders. Individually, this terminal is limited to 1 amp. 

Combined, this terminal and AUX PWR+ are limited to 2 amps 

total current.

COM

Common negative wire of powered devices such as motion 

detectors and smoke detectors.

AUX PWR +

Connect positive wire of all powered devices except smoke 

detectors and keypads. Individually, this terminal is limited to 

1 amp. Combined, this terminal and KP POS are limited to 2 

amps total current.

ZONE 6

Connect to one side of zone 6 loop. Connect the other side to 

com terminal. Open or short causes alarm. Only zone 6 can 

be used for a two-wire smoke detector, connected with a 680 

ohm EOL resistor.  Refer to the wiring diagram. Program loca-

tion 37, segment 6, option 1. Only zone 6 can be a two-wire 

zone.

COM

Common (-) terminal for zones 5 and 6.

ZONE 5

Connect to one side of zone 5 loop. Connect the other side to 

COM terminal. Open or short causes alarm.

ZONES 1 to 

4

Connect as described for zones 5 and 6.

AUXOUT 4 

(SMOKE +)

Smoke detector power 12 VDC (for those jurisdictions which 

allow the Priority zone to be used with smoke detectors). 

Current limited to 250 mA when output is positive and 250 uA 

when output is negative. This output defaults to Smoke 

Power, but can be reconfigured. Zone 7 may be used for a 2-

wire smoke detector using a 680 ohm EOL resistor.

AUXOUT 1 

to 3

Connect negative lead of low current device [relay, LED 

(install 1kohm resistor in series with LED), etc.] Connect posi-

tive lead of device to COM. Current is limited to 50 mA when 

output is negative, and 250 uA when output is positive.

Summary of Contents for NetworX NX-6V2

Page 1: ...resistor may be required across the bell terminals when a 12 VDC siren is used If no resistor is used you may experience voltage leakage into the siren which will cause these devices to output a smal...

Page 2: ...revious location Press the Medical key for the same location 5 To review the data in a specific location repeat the above procedure pressing but with no numeric data entry Each time you press the prog...

Page 3: ...numerical data Use this loca tion to program the communicator format used to transmit to the receiver connected to phone 1 Refer to your central station receiver documentation to determine which form...

Page 4: ...eless sensor missing and restore 4 Wireless sensor low battery and restore 5 Expander trouble and restore 6 Fail to communicate 7 Zone activity monitor 8 Reserved Location 18 Custom communicator forma...

Page 5: ...d no entry or exit delay is being timed It is delayed during entry and exit delay times This zone automatically bypasses if enabled in segment 1 This zone type is used to enable the tamper on a wirele...

Page 6: ...operate over the voltage range of 11 5 to 12 4 V Compatible listed devices special applications Bell output sirens Wheelock models NS 1215W NS 121575W NS4 1215W NS4 121575W AS 1215W AS 121575W Horn s...

Page 7: ...e only with a Panasonic LC12V4BP or Yuasa NP4 12 battery There is a risk of explosion if the battery is replaced with an incorrect type WARNING If separate power supplies are necessary to accommodate...

Page 8: ...are always enabled Enabled disabled for remote arming Entry delays b b Combined abort window time and entry delay must not exceed one minute Entry 1 delay 24 1 30 30 to 240 seconds Entry 2 delay 24 3...

Reviews: