"OK", "Alarm") of each LED can also be read under a common monitored data view for
programmable LEDs.
The LED status also provides a means for resetting the individual LED via
communication. The LED can also be reset from configuration with the
RESET
input.
The resetting and clearing function for all LEDs is under the
Clear
menu.
The menu structure for the programmable LEDs is presented in
. The common
color selection setting
Alarm colour
for all
ALARM
inputs is in the
General
menu, while
the LED-specific settings are under the LED-specific menu nodes.
Alarm mode
Description
LED 1
Programmable LEDs
Alarm color
Red
Green
Follow-S
Follow-F
Latched-S
LatchedAck-F-S
Programmable LED description
LED 2
General
GUID-0DED5640-4F67-4112-9A54-E8CAADFFE547 V1 EN
Figure 13:
Menu structure
Alarm mode alternatives
The
ALARM
input behavior can be selected with the alarm mode settings from the
alternatives "Follow-S", "Follow-F", "Latched-S" and "LatchedAck-F-S". The
OK
input
behavior is always according to "Follow-S". The alarm input latched modes can be cleared
with the reset input in the application logic.
GUID-58B6C3F2-873A-4B13-9834-9BB21FCA5704 V1 EN
Figure 14:
Symbols used in the sequence diagrams
"Follow-S": Follow Signal, ON
In this mode
ALARM
follows the input signal value, Non-latched.
1MAC059074-MB A
Section 3
Basic functions
615 series ANSI
77
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......