Name
Type
Description
CMD_FAIL_AL
BOOLEAN
CB closing request failed
LLDB
BOOLEAN
Live Line, Dead Bus
LLLB
BOOLEAN
Live Line, Live Bus
DLLB
BOOLEAN
Dead Line, Live Bus
DLDB
BOOLEAN
Dead Line, Dead Bus
9.3.7
Settings
Table 897:
25 Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Live dead mode
-1=Disable
1=Both Dead
2=Live L, Dead B
3=Dead L, Live B
4=Dead Bus, L Any
5=Dead L, Bus Any
6=One Live, Dead
7=Not Both Live
1=Both Dead
Energizing check mode
Difference voltage
0.01...0.50
xUn
0.01
0.05
Maximum voltage difference limit
Difference frequency
0.001...0.100
xFn
0.001
0.001
Maximum frequency difference limit
Difference angle
5...90
deg
1
5
Maximum angle difference limit
Table 898:
25 Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=enable
5=disable
1=enable
Operation Disable / Enable
Synchro check mode
1=Disable
2=Synchronous
3=Asynchronous
3=Asynchronous
Synchro check operation mode
Dead line value
0.1...0.8
xUn
0.1
0.2
Voltage low limit line for energizing check
Live line value
0.2...1.0
xUn
0.1
0.8
Voltage high limit line for energizing check
Dead bus value
0.1...0.8
xUn
0.1
0.2
Voltage low limit bus for energizing check
Live bus value
0.2...1.0
xUn
0.1
0.5
Voltage high limit bus for energizing check
Max energizing V
0.50...1.15
xUn
0.01
1.05
Maximum voltage for energizing
1MAC059074-MB A
Section 9
Control functions
615 series ANSI
989
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......