Section 6
Supervision functions
6.1
Trip circuit supervision TCM
6.1.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Trip circuit supervision
TCSSCBR
TCS
TCM
6.1.2
Function block
A070788-ANSI V1 EN
Figure 425:
Function block
6.1.3
Functionality
The trip circuit supervision function TCM is designed to supervise the control circuit of
the circuit breaker. The invalidity of a control circuit is detected by using a dedicated
output contact that contains the supervision functionality. The failure of a circuit is
reported to the corresponding function block in the relay configuration.
The function picks up and trips when TCM detects a trip circuit failure. The operating time
characteristic for the function is of the definite time (DT) type. The function trips after a
predefined operating time and resets when the fault disappears.
The function contains a blocking functionality. Blocking deactivates the
ALARM
output
and resets the timer.
6.1.4
Operation principle
The function can be enabled and disabled with the
Operation
setting. The corresponding
parameter values are “Enable” and “Disable”.
1MAC059074-MB A
Section 6
Supervision functions
615 series ANSI
835
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......