When the frequency measurement function f is unable to measure the
network frequency in the undervoltage situation, the measured values are
set to the nominal and also the quality information of the data set
accordingly. The undervoltage limit is fixed to 10 percent of the nominal
for the frequency measurement.
Limit value supervision
The limit value supervision function indicates whether the measured value of
X_INST
exceeds or falls below the set limits. The measured value has the corresponding range
information
X_RANGE
and has a value in the range of 0 to 4:
•
0: "normal"
•
1: "high"
•
2: "low"
•
3: "high-high"
•
4: "low-low"
The range information changes and the new values are reported.
GUID-AAAA7367-377C-4743-A2D0-8DD4941C585D V1 EN
Figure 466:
Presentation of operating limits
The range information can also be decoded into boolean output signals on some of the
measuring functions and the number of phases required to exceed or undershoot the limit
before activating the outputs and can be set with the
Num of phases
setting in the three-
phase measurement functions IA, IB, IC and VA, VB, VC. The limit supervision boolean
alarm and warning outputs can be blocked.
Section 8
1MAC059074-MB A
Measurement functions
900
615 series ANSI
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......