A071274-ANSI V1 EN
Figure 523:
Three shots with three initiation lines
If the sequence is initiated from the
INIT_1
line, that is, the overcurrent protection high
stage, the sequence is one shot long. If the sequence is initiated from the
INIT_2
or
INIT_3
lines, the sequence is two shots long.
Table 906:
Settings for configuration example 2
Setting name
Setting value
Shot number CBB1
1
Init signals CBB1
1 (line 1)
First reclose time
0.0s (an example)
Shot number CBB2
1
Init signals CBB2
6 (lines 2 and 3 = 2+4 = 6)
Second reclose time
0.2s (an example)
Shot number CBB3
2
Init signals CBB3
6 (lines 2 and 3 = 2+4 = 6)
Third reclose time
10.0s
9.4.6.4
Delayed initiation lines
The autoreclose function consists of six individual autoreclose initiation lines
INIT_1...INIT 6
and three delayed initiation lines:
•
DEL_INIT_2
•
DEL_INIT_3
•
DEL_INIT_4
DEL_INIT_2
and
INIT_2
are connected together with an OR-gate, as are inputs 3 and
4. Inputs 1, 5 and 6 do not have any delayed input. From the autoreclosing point of view,
it does not matter whether
INIT_x
or
DEL_INIT_x
line is used for shot initiation or
blocking.
1MAC059074-MB A
Section 9
Control functions
615 series ANSI
1023
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......