Fieldbus Independent 
I/O Modules 

2 AI Thermocouple 
750-462 (/xxx-xxx) 

Manual 

 
Version 1.0.3 

 

Summary of Contents for 750-462 Series

Page 1: ...Fieldbus Independent I O Modules 2 AI Thermocouple 750 462 xxx xxx Manual Version 1 0 3 ...

Page 2: ...0 571 8 87 5 55 Fax 49 0 571 8 87 85 55 E Mail support wago com Every conceivable measure has been taken to ensure the correctness and com pleteness of this documentation However as errors can never be fully ex cluded we would appreciate any information or ideas at any time E Mail documentation wago com We wish to point out that the software and hardware terms as well as the trademarks of companie...

Page 3: ...1 5 Scope 6 2 I O Modules 7 2 1 Analog Input Modules 7 2 1 1 750 462 xxx xxx 2 AI Thermocouple 7 2 1 1 1 View 7 2 1 1 2 Variations 8 2 1 1 3 Description 9 2 1 1 4 Display Elements 10 2 1 1 5 Schematic Diagram 10 2 1 1 6 Technical Data 11 2 1 1 7 Process Image 12 2 1 1 7 1 I O Modules for Thermocouples 12 2 1 1 7 1 1 Standard Data Format 13 2 1 1 7 2 I O Modules for Voltage Measuring mV 17 2 1 1 8 ...

Page 4: ...nufacturers are always named without referring to patent rights The existence of such rights can therefore not be ruled out 1 1 2 Personnel Qualification The use of the product detailed in this manual is exclusively geared to specialists having qualifications in PLC programming electrical specialists or persons instructed by electrical specialists who are also familiar with the valid standards WAG...

Page 5: ...ration ESD Electrostatic Discharge Warning of damage to the components by electrostatic discharge Observe the precautionary measure for handling components at risk Note Routines or advice for efficient use of the device and software optimization More information References on additional literature manuals data sheets and INTERNET pages 1 3 Number Notation Number Code Example Note Decimal 100 norma...

Page 6: ... information is to be regarded Do not use any contact spray The spray may impair the functioning of the contact area The WAGO I O SYSTEM 750 and its components are an open system It must only be assembled in housings cabinets or in electrical operation rooms Access must only be given via a key or tool to authorized qualified personnel The relevant valid and applicable standards and guidelines conc...

Page 7: ...xxx xxx 2 AI Thermocouple 2 Channel Analog Input Module for Thermocouples 2 1 1 1 View TC TC 13 14 C D B A TC TC M M S S 750 462 TC 2 Data contacts Function AI 2 TC 2 Common ground Function AI 1 TC 1 Error AI 2 Error AI 1 TC 1 Common ground Shield screen Shield screen Fig 2 1 1 1 2 Channel Analog Input Module 750 462 g046200e ...

Page 8: ...62 000 008 2 AI Thermocouple E 100 C 1000 C Diagn 2 Channel Analog Input Module Thermocouple Type E Diagn Measuring range 100 C 1000 C 750 462 000 009 2 AI Thermocouple N 100 C 1300 C Diagn 2 Channel Analog Input Module Thermocouple Type N Diagn Measuring range 100 C 1300 C 750 462 000 010 2 AI Thermocouple R 0 C 1700 C Diagn 2 Channel Analog Input Module Thermocouple Type R Diagn Measuring range ...

Page 9: ...ermocouples For example two thermocouples can be connected either to TC1 and TC1 or to TC2 and TC2 The shield screen is directly connected to the DIN rail A capacitive connection is made automatically when snapped onto the DIN rail An optocoupler is used for electrical isolation between the bus and the field side The operational readiness and trouble free internal data bus communication of the cha...

Page 10: ...1 on 750 462 000 003 off No operational readiness or the internal data bus communication is interrupted C green on Operational readiness and trouble free internal data bus communication off Normal operation 750 462 750 462 000 001 002 006 007 008 009 010 011 050 061 Overrange underflow of the admissible measuring range 13 14 C D B A D B C A Fig 2 1 1 2 Display elements g045202x D red 2 on 750 462 ...

Page 11: ...channels Measuring error 25 C Voltage input Cold junction compensation 6 K 2 K 4 K Temperature coefficient 0 2 K K Internal resistance 1 MΩ Isolation 500 V System Supply Bit width 2 x 16 bits data 2 x 8 bits control status option Dimensions mm W x H x L 12 x 64 x 100 from upper edge of 35 DIN rail Weight ca 55 g Standards and Regulations cf Chapter 2 2 of the Coupler Controller Manual CULUS UL508 ...

Page 12: ... depends on the fieldbus coupler controller used Please take this information as well as the particular design of the respective control status bytes from the section Fieldbus Specific Design of the Process Data included in the description concerning the process image of the corresponding coupler controller 2 1 1 7 1 I O Modules for Thermocouples Thermocouples 750 462 Thermocouple Type K 100 C 137...

Page 13: ...1100 0001 1000 0xFC18 1000 0x41 on 100 0 1111 1100 0001 1000 0xFC18 1000 0x00 off 0 0 0000 0000 0000 0000 0x0000 0 0x00 off 100 0 0000 0011 1110 1000 0x03E8 1000 0x00 off 200 0 0000 0111 1101 0000 0x07D0 2000 0x00 off 300 0 0000 1011 1011 1000 0x0BB8 3000 0x00 off 400 0 0000 1111 1010 0000 0x0FA0 4000 0x00 off 500 0 0001 0011 1000 1000 0x1388 5000 0x00 off 1000 0 0010 0111 0001 0000 0x2710 10000 0...

Page 14: ...0 0110 1000 0x4268 17000 0x00 off 1700 0 0100 0010 0110 1000 0x4268 17000 0x42 on 750 462 000 002 Type T Temperature Numerical value 1 Status byte LED Error C binary hex dec hex AI 1 2 ca 100 1 1111 1100 0001 0111 0xFC17 1001 0x41 on 100 0 1111 1100 0001 1000 0xFC18 1000 0x00 off 50 0 1111 1110 0000 1100 0xFE0C 500 0x00 off 0 0 0000 0000 0000 0000 0x0000 0 0x00 off 50 0 0000 0001 1111 0100 0x01F4 ...

Page 15: ...f 1200 0 0010 1110 1110 0000 0x2EE0 12000 0x00 off 1200 0 0010 1110 1110 0000 0x2EE0 12000 0x42 on 1 Temperature values below 0 C are represented in two s complement binary form 750 462 000 007 Type B Temperature Numerical value Status byte LED Error C binary hex dec hex AI 1 2 600 0 0001 0111 0111 0000 0x1770 6000 0x41 on 600 0 0001 0111 0111 0000 0x1770 6000 0x00 off 700 0 0001 1011 0101 1000 0x...

Page 16: ...111 0000 0110 0x2706 9990 0x00 off 999 0 0010 0111 0000 0110 0x2706 9990 0x42 on 1 Temperature values below 0 C are represented in two s complement binary form 750 462 000 011 Type U and 750 462 000 061 Type U without K Cold junction compensation Temperature Numerical value 1 Status byte LED Error C binary hex dec hex AI 1 2 25 0 1111 1111 0000 0110 0xFF06 250 0x41 on 25 0 1111 1111 0000 0110 0xFF...

Page 17: ...ted in two s complement binary form 2 1 1 7 2 I O Modules for Voltage Measuring mV Voltage measuring mV 750 462 000 003 Voltage measuring 120 120 mV When measuring the voltage the input range from 120 mV to 120 mV is mapped to a range of values between 18750 and 18750 with a resolution of 6 4 µV per digit Voltage values below 0 mV are represented in two s complement binary form 750 462 000 003 mV ...

Page 18: ...unded thermocouples can be connected in the following ways With grounded thermocouples the common ground M can be connected to the screen S using an external bridge so that common mode interferences can be eliminated see figure below TC TC TC TC M M S S TC TC Fig 2 1 1 4 Connection of grounded thermocouple g046204x With ungrounded thermocouples the common ground M can be connected both to the TC i...

Page 19: ...750 462 xxx xxx 2 AI Thermocouple 19 Examples of Connection WAGO I O SYSTEM 750 I O Modules ...

Page 20: ...WAGO Kontakttechnik GmbH Co KG Postfach 2880 D 32385 Minden Hansastraße 27 D 32423 Minden Phone 05 71 8 87 0 Fax 05 71 8 87 1 69 E Mail info wago com Internet http www wago com ...