UMSITRAPDS3-1
Model Designations and Specifications
November 2010
9-11
Measuring cell filling
Silicone oil or inert filling liquid; max. 160 bar a (2320 psia) with oxygen
measurement
Process connection
Connection shank G1/2A to DIN EN837-1, female thread 1/2-14 NPT or oval flange
to DIN 19213 with mounting thread M10 or 7/16-20 UNF to EN 16518
Power Supply U
H
Terminal voltage at transmitter
10.5 to 45 Vdc
10.5 to 30 Vdc in intrinsically-safe mode
Certificate and approvals
See Table 9-20
HART communication
HART communication
230 to 1100
Ω
Protocol
HART Version 5.x
Software for computer
SIMATIC PDM
Note: 3.6 psi absolute (250 mbar a) Capsule
This measuring cell is designed for operation within the measuring limits of 0 to 3.63 psi
(absolute). When stored in the normal ambient pressure of about of about 14.7 psi
(absolute), the measuring cell is in the overload state. An overload error of up to 0.03 psi
may occur. The overload disappears in normal operation within the measuring limits and
the transmitter operates within specifications.
When performing accurate continuous pressure measurements within the measuring
limits, a readjustment of the transmitter zero for absolute pressure must be performed
after approximately one day (refer to Section 6.2.5).
If pressure measurements exceed the measuring limits repeatedly (e.g. batch processes
with transitions between vacuum and ventilation), a measuring cell with a maximum
range of 18.9 psi should be selected to avoid overloading.
Содержание 7MF4033 series
Страница 48: ...Model 275 Universal Hart Communicator UMSITRPDS3 1 November 2010 2 26 ...
Страница 86: ...Installation UMSITRPDS3 1 November 2010 4 34 ...
Страница 152: ...Calibration and Maintenance UMSITRPSD3 1 November 2010 7 20 ...
Страница 158: ...Circuit Description UMSITRPDS3 1 November 2010 8 6 ...
Страница 197: ......
Страница 198: ......
Страница 200: ...Model Designations and Specifications UMSITRPDS3 1 November 2010 9 42 ...
Страница 204: ...Glossary UMSITRPDS3 1 November 2010 10 4 ...
Страница 208: ...Appendix A Online Configuration Map UMSITRPDS3 1 11 4 November 2010 ...
Страница 210: ...Appendix B Hazardous Area Installation UMSITRPDS3 1 12 2 November 2010 FIGURE 12 1 Control Drawing ...
Страница 211: ...UMSITRPDS3 1 Appendix B Hazardous Area Installation November 2010 12 3 FIGURE 12 2 Control Drawing ...
Страница 212: ...Appendix B Hazardous Area Installation UMSITRPDS3 1 12 4 November 2010 FIGURE 12 3 Control Drawing ...
Страница 216: ...Appendix C Elevation and Suppression Correction UMSITRPDS3 1 13 4 November 2010 ...