UMSITRPDS3-1
On-Line Operation
November 2010
6-9
Given
Set Zero
Set Full Scale
6.2.2.2 Practical Applications
Set Zero and Full Scale
The steps below should be followed to set the transmitter zero output current to 4 mA and the full scale
current to 20 mA.
1.
Apply a pressure representing zero.
2.
Press the M pushbutton until mode 2 appears.
3.
Set zero by pressing the
(
or
'
pushbutton to set the display to 4 mA.
4.
Press the M pushbutton to save the setting and go to mode 3.
5.
Apply a pressure representing full scale.
6.
Set full scale by pressing the
(
or
'
pushbutton to set the full scale output current value in the
display.
7.
Press the M pushbutton to save the setting.
Содержание 7MF4033 series
Страница 48: ...Model 275 Universal Hart Communicator UMSITRPDS3 1 November 2010 2 26 ...
Страница 86: ...Installation UMSITRPDS3 1 November 2010 4 34 ...
Страница 152: ...Calibration and Maintenance UMSITRPSD3 1 November 2010 7 20 ...
Страница 158: ...Circuit Description UMSITRPDS3 1 November 2010 8 6 ...
Страница 197: ......
Страница 198: ......
Страница 200: ...Model Designations and Specifications UMSITRPDS3 1 November 2010 9 42 ...
Страница 204: ...Glossary UMSITRPDS3 1 November 2010 10 4 ...
Страница 208: ...Appendix A Online Configuration Map UMSITRPDS3 1 11 4 November 2010 ...
Страница 210: ...Appendix B Hazardous Area Installation UMSITRPDS3 1 12 2 November 2010 FIGURE 12 1 Control Drawing ...
Страница 211: ...UMSITRPDS3 1 Appendix B Hazardous Area Installation November 2010 12 3 FIGURE 12 2 Control Drawing ...
Страница 212: ...Appendix B Hazardous Area Installation UMSITRPDS3 1 12 4 November 2010 FIGURE 12 3 Control Drawing ...
Страница 216: ...Appendix C Elevation and Suppression Correction UMSITRPDS3 1 13 4 November 2010 ...