UMSITRPDS3-1
On-Line Operation
November 2010
6-31
The default setting for all warnings and alarms is OFF. To set and enable:
1.
In the Online menu, press 3 Device Setup.
2.
In the Device Setup menu, press 2 Diagnostics/Service.
3.
In the Diagnostics/Service menu, press 1 Diagnosis
4.
In the Diagnosis menu, press 3 Warnings/Alarms. Refer to the Online Configuration Map in
Appendix A and to the HART Communicator’s help screens.
6.4.19.1 Operating Hours Counter
Two operating hours counters with non-volatile memories are provided for the electronics and the sensor.
These counters are not re-settable. If power is removed and later reapplied, the counters begin counting
from the previous time. To read the operating hours counters:
1.
In the Online menu, press 3 Device Setup
2.
In the Device Setup menu, press 2 Diagnosis/Service
3.
In the Diagnosis/Service menu, press1 Diagnosis
4.
In the Diagnosis menu, press 2 Operating Hours
5.
In the Operating Hours menu, press 1 Operating Hours Electronics or 2 Operating Hours Sensor. The
total operating hours will be displayed.
6.4.19.2 Calibration Timer and Service Timer
A two-stage time can be set to ensure regular calibration of the electronics and servicing of the
transmitter. A calibration or service warning appears after the first time expires. On expiration of a second
time, set as a time difference, a diagnostic alarm is signaled and a fault current is output.
A warning or alarm must be acknowledged before work can be performed on the transmitter. Timers can
then be reset and switched off temporarily.
For operating/acknowledging warnings and alarms in the HART Communicator, the following applies:
As long as the warning/alarm limit has not been reached:
•
“Reset” resets the timer and begins again with the counter at 0. Monitoring is still active.
•
“Acknowledge” has no effect, the timer continues running and the monitoring is still active.
•
“Reset and deactivate” stops the timer, resets it, and deactivates the monitoring.
When the warning/alarm limit has been reached:
•
“Acknowledge” resets the warning/alarm message but the timer continues to run. In this state, no new
alarm or warning is possible since the time limits will still have to be exceeded.
•
“Reset” resets the warning/alarm message the timer. At the same time, the alarm or warning is
acknowledged. The timer runs again immediately from zero and will respond again when the
warning/alarm limit is exceeded. The next calibration interval is therefore immediately activated.
•
“Reset and ActivateW/A” resets the warning/alarm message and resets and deactivated the timer.
Содержание 7MF4033 series
Страница 48: ...Model 275 Universal Hart Communicator UMSITRPDS3 1 November 2010 2 26 ...
Страница 86: ...Installation UMSITRPDS3 1 November 2010 4 34 ...
Страница 152: ...Calibration and Maintenance UMSITRPSD3 1 November 2010 7 20 ...
Страница 158: ...Circuit Description UMSITRPDS3 1 November 2010 8 6 ...
Страница 197: ......
Страница 198: ......
Страница 200: ...Model Designations and Specifications UMSITRPDS3 1 November 2010 9 42 ...
Страница 204: ...Glossary UMSITRPDS3 1 November 2010 10 4 ...
Страница 208: ...Appendix A Online Configuration Map UMSITRPDS3 1 11 4 November 2010 ...
Страница 210: ...Appendix B Hazardous Area Installation UMSITRPDS3 1 12 2 November 2010 FIGURE 12 1 Control Drawing ...
Страница 211: ...UMSITRPDS3 1 Appendix B Hazardous Area Installation November 2010 12 3 FIGURE 12 2 Control Drawing ...
Страница 212: ...Appendix B Hazardous Area Installation UMSITRPDS3 1 12 4 November 2010 FIGURE 12 3 Control Drawing ...
Страница 216: ...Appendix C Elevation and Suppression Correction UMSITRPDS3 1 13 4 November 2010 ...