UMSITRPDS3-1
Introduction
November 2010
1-9
1.3 RATING, APPROVAL, AND TAG PLATES
These plates are fastened to the outside of the transmitter
enclosure, as shown at right. The rating plate shows that
transmitter’s model number, serial number, and performance
data. The approval plate shows that transmitter’s approval and
certification data. Always refer to these plates to confirm the
model number, performance data and approval and certification
data before installing or servicing a transmitter. Representative
plates are shown below.
The tag plate is fastened with two screws so it can be
removed for engraving.
SIEMENS
Springhouse, PA USA
SITRANS P
Transmitter for diff. pressure
7MF4433-1EA22-1NC6-Z
B21
Fab. Nr. IX-T411-9014869
V
H
:DC 10.5-45V (not intr. safe) outp.: 4-20 mA
Mat.: Connec. Diaphr. O-ring Filling
1.4404 FPM Silicon oil
Measuring span : 2.4 - 240 inH2O
Rated pressure : MWP 2300 psi
Type of protection IP 65
MG
0038
4b
1
2
PED:SEP
Assembled in USA / Components of France
SIEMENS
Springhouse, PA USA
SITRANS P
(XP/DIP) or (IS)
CL I ZN 0/1 AEx ia IIC T4..T6 (FM)
Ex ia IIC T4..T6 (CSA cert.2000.1153651)
CL I DIV 1, GP ABCD T4..T6; CL II, DIV 1, GP EFG; CL III
Vi <
30V :
Ii <
100 mA :
Pi <
0.75 W
Ci <
6 nF :
Li <
0.4 mH
Vmax = 30 V
Ta = T4: -40..85ºC ; T6: -40..60ºC
ENCL Type 4X, seal not required
FW: 0011.03.06 HW: 02.05.01
FM
APPROVED
MG
0038
4b
Per Control Dwg. A5E00072770A
CL 1 Div 2 GP ABCD T4..T6
CL II DIV 2 GP FG; CL III
Assembled in USA / Components of France
Rating Plate
1 Model number
2 Serial number
Approval Plate
1.4 CONFIGURATION
A transmitter must be configured before use. Each transmitter is shipped with either a default
configuration or, if specified at time of order, a custom configuration defined by the user. The default
configuration may need to be edited before the transmitter is used in a loop. The configuration is stored
within the transmitter in a non-volatile memory.
A configuration can be created or edited locally at the transmitter’s magnetic pushbuttons or remotely
using the Model 275 HART Communicator.
1
2
+
+
M
G
0035
3a
3
1 Rating plate
2 Approval plate
3 Tag plate
Note: If using a Model 375 Field Communicator, see the inside of the front
cover of this manual.
Содержание 7MF4033 series
Страница 48: ...Model 275 Universal Hart Communicator UMSITRPDS3 1 November 2010 2 26 ...
Страница 86: ...Installation UMSITRPDS3 1 November 2010 4 34 ...
Страница 152: ...Calibration and Maintenance UMSITRPSD3 1 November 2010 7 20 ...
Страница 158: ...Circuit Description UMSITRPDS3 1 November 2010 8 6 ...
Страница 197: ......
Страница 198: ......
Страница 200: ...Model Designations and Specifications UMSITRPDS3 1 November 2010 9 42 ...
Страница 204: ...Glossary UMSITRPDS3 1 November 2010 10 4 ...
Страница 208: ...Appendix A Online Configuration Map UMSITRPDS3 1 11 4 November 2010 ...
Страница 210: ...Appendix B Hazardous Area Installation UMSITRPDS3 1 12 2 November 2010 FIGURE 12 1 Control Drawing ...
Страница 211: ...UMSITRPDS3 1 Appendix B Hazardous Area Installation November 2010 12 3 FIGURE 12 2 Control Drawing ...
Страница 212: ...Appendix B Hazardous Area Installation UMSITRPDS3 1 12 4 November 2010 FIGURE 12 3 Control Drawing ...
Страница 216: ...Appendix C Elevation and Suppression Correction UMSITRPDS3 1 13 4 November 2010 ...