Chapter 4: Connecting External Equipment (Optional)
50
Connecting a DPX2 Sensor Package to DPX3
You can connect only one DPX2 sensor package to the "end" of a DPX3
sensor chain. It is strongly recommended to use an RJ-12 to RJ-45
adapter for connecting the DPX2 to the final DPX3 in the chain.
The maximum number of DPX3 sensor packages in the chain must be
less than 12 when a DPX2 sensor package is involved.
When connecting a DPX2 sensor package containing three DPX2
sensors:
A maximum of nine DPX3 sensor packages can be cascaded because
12-3=9.
When connecting a DPX2 sensor package containing two DPX2
sensors:
A maximum of ten DPX3 sensor packages can be cascaded because
12-2=10.
When connecting a DPX2 sensor package containing one DPX2
sensor:
A maximum of eleven DPX3 sensor packages can be cascaded
because 12-1=11.
Содержание EMX2-111
Страница 69: ...Chapter 4 Connecting External Equipment Optional 57...
Страница 78: ...Chapter 5 Using the EMX 66 EMX2 888...
Страница 442: ...Appendix A Specifications 430 RS 485 Pin signal definition 6 D bi direction al Data 7 8...
Страница 488: ...Appendix E LDAP Configuration Illustration 476 2 The EMX_Admin role is created...
Страница 507: ...Appendix G RADIUS Configuration Illustration 495 Note If your EMX uses PAP then select PAP...
Страница 508: ...Appendix G RADIUS Configuration Illustration 496 10 Select Standard to the left of the dialog and then click Add...
Страница 509: ...Appendix G RADIUS Configuration Illustration 497 11 Select Filter Id from the list of attributes and click Add...
Страница 512: ...Appendix G RADIUS Configuration Illustration 500 14 The new attribute is added Click OK...
Страница 513: ...Appendix G RADIUS Configuration Illustration 501 15 Click Next to continue...