Chapter 4: Connecting External Equipment (Optional)
51
DX Sensor Packages
Most DX sensor packages contain terminals for connecting detectors or
actuators. For information on connecting actuators or detectors to DX
terminals, refer to the Environmental Sensors Guide or Online Help on
Raritan website's
Support page
(
You can cascade up to 12 DX sensor packages.
When cascading DX, remember that the EMX only supports a maximum
of 32 sensors and/or actuators.
If there are more than 32 sensors and/or actuators connected, every
sensor and/or actuator after the 32nd one is NOT managed by the EMX.
For example, if you cascade 12 DX packages, and each package contains
3 functions (a function is a sensor or actuator), the EMX does NOT
manage the last 4 functions because the total 36 (12*3=36) exceeds 32 by
4.
Tip: To manage the last 4 functions, you can release 4 "managed"
sensors or actuators, and then manually bring the last 4 functions into
management. See
Peripherals
Numbers
Components
RJ-45 ports, each of which is located on
either end of a DX sensor package.
RJ-12 port, which is reserved for future
use and now blocked.
Removable rackmount brackets.
Connect DX to the EMX:
1.
Connect an RJ-12 to RJ-45 adapter cable which is shipped with a DX
sensor package to the DX.
Connect the adapter's RJ-45 connector to either RJ-45 port of
the DX.
2.
If you want to cascade DX packages, get an additional standard
network patch cable (CAT5e or higher) and then:
Содержание EMX2-111
Страница 69: ...Chapter 4 Connecting External Equipment Optional 57...
Страница 78: ...Chapter 5 Using the EMX 66 EMX2 888...
Страница 442: ...Appendix A Specifications 430 RS 485 Pin signal definition 6 D bi direction al Data 7 8...
Страница 488: ...Appendix E LDAP Configuration Illustration 476 2 The EMX_Admin role is created...
Страница 507: ...Appendix G RADIUS Configuration Illustration 495 Note If your EMX uses PAP then select PAP...
Страница 508: ...Appendix G RADIUS Configuration Illustration 496 10 Select Standard to the left of the dialog and then click Add...
Страница 509: ...Appendix G RADIUS Configuration Illustration 497 11 Select Filter Id from the list of attributes and click Add...
Страница 512: ...Appendix G RADIUS Configuration Illustration 500 14 The new attribute is added Click OK...
Страница 513: ...Appendix G RADIUS Configuration Illustration 501 15 Click Next to continue...