Chapter 8: Using the Command Line Interface
322
Setting Data Logging Measurements Per Entry
This command defines the number of measurements accumulated per
log entry.
config:#
emd measurementsPerLogEntry <number>
Variables:
<number> is an integer between 1 and 600. The default is 60
samples per log entry.
For more information, see
Setting Data Logging
(on page 245).
Specifying the Device Altitude
This command specifies your EMX device's altitude above sea level (in
meters). You must specify the EMX device's altitude above sea level if a
Raritan's DPX differential air pressure sensor is attached. This is
because the device's altitude is associated with the altitude correction
factor. See
Altitude Correction Factors
(on page 532).
config:#
emd deviceAltitude <altitude>
Variables:
<altitude> is an integer between 1 and 3000 meters.
Setting the Z Coordinate Format for Environmental Sensors
This command enables or disables the use of rack units for specifying
the height (Z coordinate) of environmental sensors.
config:#
emd externalSensorsZCoordinateFormat <option>
Variables:
<option> is one of the options:
rackUnits or freeForm.
Option
Description
rackUnits
The height of the Z coordinate is measured in
standard rack units. When this is selected, you
can type a numeric value in the rack unit to
describe the Z coordinate of any environmental
sensors or actuators.
Содержание EMX2-111
Страница 69: ...Chapter 4 Connecting External Equipment Optional 57...
Страница 78: ...Chapter 5 Using the EMX 66 EMX2 888...
Страница 442: ...Appendix A Specifications 430 RS 485 Pin signal definition 6 D bi direction al Data 7 8...
Страница 488: ...Appendix E LDAP Configuration Illustration 476 2 The EMX_Admin role is created...
Страница 507: ...Appendix G RADIUS Configuration Illustration 495 Note If your EMX uses PAP then select PAP...
Страница 508: ...Appendix G RADIUS Configuration Illustration 496 10 Select Standard to the left of the dialog and then click Add...
Страница 509: ...Appendix G RADIUS Configuration Illustration 497 11 Select Filter Id from the list of attributes and click Add...
Страница 512: ...Appendix G RADIUS Configuration Illustration 500 14 The new attribute is added Click OK...
Страница 513: ...Appendix G RADIUS Configuration Illustration 501 15 Click Next to continue...