Chapter 8: Using the Command Line Interface
406
Specifying the Rack Unit Numbering Mode
This command syntax specifies the numbering mode of rack units on the
asset strips connected to the EMX device. The numbering mode changes
the rack unit numbers.
config:#
assetStrip <n> rackUnitNumberingMode <mode>
Variables:
<n> is the number of the FEATURE port where the selected asset
strip is physically connected. For the EMX device with only one
FEATURE port, the number is always 1.
<mode> is one of the numbering modes:
topDown or bottomUp.
Mode
Description
topDown
The rack units are numbered in the ascending
order from the highest to the lowest rack unit.
bottomUp
The rack units are numbered in the descending
order from the highest to the lowest rack unit.
Specifying the Rack Unit Numbering Offset
This command syntax specifies the starting number of rack units on the
asset strips connected to the EMX device.
config:#
assetStrip <n> rackUnitNumberingOffset <number>
Variables:
<n> is the number of the FEATURE port where the selected asset
strip is physically connected. For the EMX device with only one
FEATURE port, the number is always 1.
<number> is a starting number for numbering rack units on the
connected asset strip. This value is an integer number.
Содержание EMX2-111
Страница 69: ...Chapter 4 Connecting External Equipment Optional 57...
Страница 78: ...Chapter 5 Using the EMX 66 EMX2 888...
Страница 442: ...Appendix A Specifications 430 RS 485 Pin signal definition 6 D bi direction al Data 7 8...
Страница 488: ...Appendix E LDAP Configuration Illustration 476 2 The EMX_Admin role is created...
Страница 507: ...Appendix G RADIUS Configuration Illustration 495 Note If your EMX uses PAP then select PAP...
Страница 508: ...Appendix G RADIUS Configuration Illustration 496 10 Select Standard to the left of the dialog and then click Add...
Страница 509: ...Appendix G RADIUS Configuration Illustration 497 11 Select Filter Id from the list of attributes and click Add...
Страница 512: ...Appendix G RADIUS Configuration Illustration 500 14 The new attribute is added Click OK...
Страница 513: ...Appendix G RADIUS Configuration Illustration 501 15 Click Next to continue...