431
You can accomplish part or all of the following tasks simultaneously by
plugging a USB flash drive which contains one or several special
configuration files into the EMX.
Configuration changes
Firmware upgrade
Downloading diagnostic data
Tip: You can also accomplish the same tasks via the TFTP server in a
DHCP network. See
Bulk Configuration or Firmware Upgrade via
DHCP/TFTP
(on page 442).
In This Chapter
System and USB Requirements.............................................................. 430
Configuration Files .................................................................................. 431
Firmware Upgrade via USB..................................................................... 440
System and USB Requirements
You must satisfy ALL of the following requirements prior to using a USB
flash drive to perform device configuration and/or firmware upgrade.
EMX system requirements:
There is at least one USB-A port available on your Raritan device.
Your EMX must be version 2.2.13 or later.
Note that the EMX interpreted the USB drive's contents using the
firmware which was running when plugging the USB drive, not the
new firmware after firmware upgrade.
USB drive requirements:
The drive contains either a single partition formatted as a Windows
FAT32 filesystem, or NO partition tables (that is, a
superfloppy-formatted drive).
The drive contains a configuration file called
fwupdate.cfg in its root
directory. See
fwupdate.cfg
(on page 432).
Appendix B Configuration or Firmware Upgrade
with a USB Drive
Содержание EMX2-111
Страница 69: ...Chapter 4 Connecting External Equipment Optional 57...
Страница 78: ...Chapter 5 Using the EMX 66 EMX2 888...
Страница 442: ...Appendix A Specifications 430 RS 485 Pin signal definition 6 D bi direction al Data 7 8...
Страница 488: ...Appendix E LDAP Configuration Illustration 476 2 The EMX_Admin role is created...
Страница 507: ...Appendix G RADIUS Configuration Illustration 495 Note If your EMX uses PAP then select PAP...
Страница 508: ...Appendix G RADIUS Configuration Illustration 496 10 Select Standard to the left of the dialog and then click Add...
Страница 509: ...Appendix G RADIUS Configuration Illustration 497 11 Select Filter Id from the list of attributes and click Add...
Страница 512: ...Appendix G RADIUS Configuration Illustration 500 14 The new attribute is added Click OK...
Страница 513: ...Appendix G RADIUS Configuration Illustration 501 15 Click Next to continue...