Appendix H: Additional EMX Information
538
Symptom
Probable cause
Failure to access a slave device
Network connection to the master device is lost.
The cascading cable connected to the slave device in
question or any upstream device (if available) is loose or
lost.
No power is supplied to the slave device in question or
any upstream devices.
The Ethernet or wireless interface on the master device
is disabled.
IPv4 (or IPv6) settings are disabled on the slave device in
question.
The cascading mode of the slave device in question or
any upstream device is set incorrectly. For example, the
master device is set to Bridging, but one of the slave
devices is set to Port Forwarding.
In the port forwarding mode, the master device's role is
incorrectly set to 'Slave'.
In the port forwarding mode, the master device's
downstream interface is incorrectly set. For example,
you use a USB cable to connect the 1st slave device, but
select the Ethernet port as the downstream interface.
In the port forwarding mode, the role of the slave device
in question or any upstream device is set to 'Master'
instead of 'Slave'.
In the port forwarding mode, the port number you added
to the IP address is incorrect. See
Port Number Syntax
(on page 165).
The firmware version of the slave device in question or
any upstream device is older than 3.3.10.
Tip: To determine which EMX may be the failure point of network, you
may ping each EMX in the cascading chain, or check the slave-related
events in the event log of each EMX. See
Slave Connection and
Disconnection Events
(on page 538).
Содержание EMX2-111
Страница 69: ...Chapter 4 Connecting External Equipment Optional 57...
Страница 78: ...Chapter 5 Using the EMX 66 EMX2 888...
Страница 442: ...Appendix A Specifications 430 RS 485 Pin signal definition 6 D bi direction al Data 7 8...
Страница 488: ...Appendix E LDAP Configuration Illustration 476 2 The EMX_Admin role is created...
Страница 507: ...Appendix G RADIUS Configuration Illustration 495 Note If your EMX uses PAP then select PAP...
Страница 508: ...Appendix G RADIUS Configuration Illustration 496 10 Select Standard to the left of the dialog and then click Add...
Страница 509: ...Appendix G RADIUS Configuration Illustration 497 11 Select Filter Id from the list of attributes and click Add...
Страница 512: ...Appendix G RADIUS Configuration Illustration 500 14 The new attribute is added Click OK...
Страница 513: ...Appendix G RADIUS Configuration Illustration 501 15 Click Next to continue...