17. APPLICATION OF FUNCTIONS
17 - 23
No.
Symbol
Name and function
Initial
value
[unit]
Setting
range
PX25
*TDS
Tough drive setting
Alarms may not be avoided with the tough drive function depending on the situations of the
power supply and load fluctuation.
You can assign MTTR (During tough drive) to pins CN3-9, CN3-13, and CN3-15 with [Pr.
PD07] to [Pr. PD09].
Refer to the
"Name and
function" column.
Setting
digit
Explanation
Initial
value
_ _ _ x
For manufacturer setting
0h
_ _ x _
Vibration tough drive selection
0: Disabled
1: Enabled
Selecting "1" enables to suppress vibrations by automatically
changing setting values of [Pr. PB13 Machine resonance
suppression filter 1] and [Pr. PB15 Machine resonance suppression
filter 2] in case that the vibration exceeds the value of the oscillation
level set in [Pr. PX26].
Refer to (8) in this section for details.
0h
_ x _ _
SEMI-F47 function selection
0: Disabled
1: Enabled
Selecting "1" enables to avoid triggering [AL. 10 Undervoltage]
using the electrical energy charged in the capacitor in case that an
instantaneous power failure occurs during operation. In [Pr. PX28
SEMI-F47 function - Instantaneous power failure detection time],
set the time until the occurrence of [AL. 10.1 Voltage drop in the
control circuit power].
0h
x _ _ _
For manufacturer setting
0h
PX26 OSCL1 Vibration tough drive - Oscillation detection level
Set a filter readjustment sensitivity of [Pr. PB13 Machine resonance suppression filter 1] and
[Pr. PB15 Machine resonance suppression filter 2] while the vibration tough drive is enabled.
However, setting "0" will be 50%.
Example: When you set "50" to the parameter, the filter will be readjusted at the time of 50%
or more oscillation level.
50
[%]
0
to
100
PX27 *OSCL2 Vibration tough drive function selection
Refer to the
"Name and
function" column.
Setting
digit
Explanation
Initial
value
_ _ _ x
Oscillation detection alarm selection
0: [AL. 54 Oscillation detection] will occur at oscillation detection.
1: [AL. F3.1 Oscillation detection warning] will occur at oscillation
detection.
2: Oscillation detection function disabled
Select alarm or warning when an oscillation continues at a filter
readjustment sensitivity level of [Pr. PX26].
The digit is continuously enabled regardless of the vibration tough
drive in [Pr. PX25].
0h
_ _ x _
For manufacturer setting
0h
_ x _ _
0h
x _ _ _
0h
Содержание MR-J4-100B(-RJ)
Страница 17: ...8 MEMO ...
Страница 143: ...4 STARTUP 4 20 MEMO ...
Страница 199: ...5 PARAMETERS 5 56 MEMO ...
Страница 227: ...6 NORMAL GAIN ADJUSTMENT 6 28 MEMO ...
Страница 281: ...8 TROUBLESHOOTING 8 16 MEMO ...
Страница 303: ...9 DIMENSIONS 9 22 MEMO ...
Страница 319: ...10 CHARACTERISTICS 10 16 MEMO ...
Страница 429: ...11 OPTIONS AND PERIPHERAL EQUIPMENT 11 110 MEMO ...
Страница 435: ...12 ABSOLUTE POSITION DETECTION SYSTEM 12 6 MEMO ...
Страница 483: ...14 USING A LINEAR SERVO MOTOR 14 34 MEMO ...
Страница 531: ...16 FULLY CLOSED LOOP SYSTEM 16 26 MEMO ...
Страница 613: ...17 APPLICATION OF FUNCTIONS 17 82 MEMO ...
Страница 653: ...APPENDIX App 40 This certificate is valid until 2017 02 28 After March 2017 use certificate shown on the previous page ...
Страница 654: ...APPENDIX App 41 ...